R Series 1/2/3 kVA

Reliable power supply for small and medium enterprises

Delta’s Amplon R series is an online double-conversion rack-mountable UPS providing consistent sine-wave power to your critical equipment and reliable protection for IT equipment and data centers. The R series offers an output power factor of 0.9 and a best-in-class AC-AC efficiency of up to 93% for greater energy savings. The Amplon R series leads the industry in combining compact size, availability, flexibility, and low total cost of ownership.

Delta R 1/2/3 kVA UPS - LCD panel
Product available regions :

North America Latin America
 


Downloads (EN) Downloads (PT) Downloads (ES) Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Availability

  • True online double-conversion topology provides zero transfer time to ensure maximum protection of the equipment
  • Watch-dog design of the DSP (Digital Signal Processor) increases reliability
  • Cold-start capability provides temporary battery power when the utility power is out
  • Operating temperature tolerance up to 50°C ensures critical loads’ continuity
  • The Maintenance Bypass Box offers load continuity during battery replacement or other upgrades
 

Flexibility

  • Compact dimensions meet the needs of different rack cabinets
  • Convertible rack and tower configuration in 2U size cabinet
  • Excellent local communications through rotatable LCD display
  • Intelligent management software connectivity via RS232, mini slot or USB port
 

Low Total Cost of Ownership

  • Wide input voltage range reduces the chance of using the battery and extends battery life
  • Intelligent battery management sustains battery life and performance
  • High output power factor of 0.9 provides more real power to critical loads
  • High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 3%) save upstream investment
  • Up to 93% AC-AC efficiency and 96% efficiency in ECO mode results in marked energy cost savings
  • Fan speed control by load level and room temperature optimizes performance
Applications

UPS R series applications

Specifications
  1. Model
  2. R-1K / R-2K / R-3K

  3. Power Rating
  4. R-1K: 1 kVA / 0.9 kW
    R-2K: 2 kVA / 1.8 kW
    R-3K: 3 kVA / 2.7 kW

  5. Input
  6. Nominal Voltage: 200*/208*/220/230/240 Vac
  7. Voltage Range
    175~280 Vac (full load)
    80~175 Vac (50~100% load)
  8. Frequency: 50/60 Hz ± 10 Hz
  9. Power Factor: > 0.99 (full load)
  10. Current Harmonic Distortion: < 3%

  11. Output
  12. Power Factor: 0.9
  13. Voltage: 200*/208*/220/230/240 Vac
  14. Voltage Regulation: ± 1% (linear load)
  15. Frequency: 50/60 Hz ± 0.05 Hz
  16. Overload Capability
    < 105%: Continuous
    105~125%: 1 minute
    125~150%: 30 seconds
  17. Receptacle
    R-1K: IEC C13 x 4 / Brazil standard x 3 / Argentina standard x 3
    R-2K: IEC C13 x 6, IEC C19 x 1 / Brazil standard x 4 / Argentina standard x 4
    R-3K: IEC C13 x 6, IEC C19 x 1 / Brazil standard x 4 / Argentina standard x 4

  18. Efficiency
  19. AC-AC
    R-1K: 91%
    R-2K/3K: Up to 93%
  20. ECO Mode
    R-1K: 95%
    R-2K/3K: Up to 96%

  21. Battery
  22. Battery Voltage
    R-1K: 24 Vdc
    R-2K: 48 Vdc
    R-3K: 72 Vdc
  23. Charge Current: 1.5 A

  24. Audible Noise **
    R-1K: < 40 dB
    R-2K/3K: < 43 dB

  25. Display: LCD display and LED indicators

  26. Communication Interfaces
  27. Standard: Mini Slot x 1, RS-232 Port x 1, USB Port x 1

  28. Conformance
  29. Safety: CE

  30. Physical
  31. Dimensions (W x D x H)
    R-1K
    UPS : 440 x 335 x 88 mm
    Battery : 440 x 335 x 88 mm
  32. R-2K
    UPS : 440 x 430 x 88 mm
    Battery : 440 x 430 x 88 mm
  33. R-3K
    UPS : 440 x 565 x 88 mm
    Battery : 440 x 565 x 88 mm
  34. Weight
    R-1K
    UPS : 11.5 kg
    Battery : 18.8 kg
  35. R-2K
    UPS : 20.6 kg
    Battery : 30.3 kg
  36. R-3K
    UPS : 27.5 kg
    Battery : 54.1 kg

  37. Environment
  38. Operating Temperature: 0~50°C ***
  39. Relative Humidity: 5~95% (non-condensing)

  40. * When the UPS is de-rated to 90% of its capacity.
    ** If the UPS is running at < 75% load and in room temperature.
    *** When the operating temperature is at 40~50°C, the UPS will be de-rated to 80% of its capacity.

    All specifications are subject to change without prior notice.


Run Time
Power Rating Internal Battery External Battery Cabinet Quantity Run time at different load (mins)
25% 50% 75% 100%
1 kVA Yes 0 22.1 10.7 6.6 3.8
1 85.0 43.2 26.2 18.8
2 150.5 79.7 49.8 34.8
3 216.5 117.1 74.5 52.9
2 kVA Yes 0 22.7 11.1 6.9 4.2
1 87.3 44.9 27.6 19.0
2 154.6 82.8 52.5 36.7
3 222.3 121.6 78.4 55.7
3 kVA Yes 0 24.7 11.4 6.9 4.2
1 94.5 46.1 27.6 19.0
2 167.0 84.9 52.5 36.7
3 239.8 124.5 78.4 55.7