RT Series 5/6/8/10 kVA (208 V)

A total solution for reliable power with high availability and performance

The Amplon RT Series 5-10 kVA is an online double-conversion UPS that provides an output power factor of up to unity to enable the maximum capacity for more critical loads. Outstanding energy savings can be achieved based on an AC-AC efficiency of up to 95.5% and 98.5% in ECO mode. The Amplon RT Series 5-10 kVA offers a total solution with the Standard Runtime models including an in-built battery, power distribution box and maintenance bypass breaker. It provides a complete and practical package that can be used on the critical loads right away. This series offers advanced performance for various applications such as servers, data centers, network, VoIP and telecommunication. The parallel capacity of up to four units enables higher reliability for mission critical applications.

 RT Series UPS, Single Phase, 5/6/8/10 kVA, 208V
 
Product available regions :

North America Latin America
(5–20 kVA)


Downloads Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Availability & Flexibility

  • True online double-conversion topology and zero transfer time to battery provides 24/7 full-time protection
  • Up to four units parallel capacity allows redundancy and load expansion; Extended Runtime models only
  • Component life prediction, such as fan life prediction, can monitor operating conditions before failure or downtime occurs
  • Automatic fan speed control maximizes system efficiency and significantly reduces audible noise; fan failure detection sends an early warning when the fan stops
  • VRLA and Li-ion External Battery Cabinet (EBC) are optional for scalable runtime
  • Li-ion battery compatibility and flexible battery quantity enable better usability and convenience
  • AC-start function allows the UPS to be switched on without connecting to a battery
  • Programmable load bank disconnects non-critical loads when a blackout occurs and reserves more battery power for critical loads

Low Total Cost of Ownership

  • Output power factor up to unity guarantees no de-rating with loads and provides permanent 100% kW
  • High AC-AC efficiency of up to 95.5% and 98.5% in ECO mode lowers energy costs
  • Wide input voltage range and protection against over voltage prolongs battery life
  • The Power Distribution Box (PDB) and Maintenance Bypass Breaker (MBB) which are default to Standard Runtime models enable simple configuration
  • Automatic fan speed control maximizes system efficiency and significantly reduces audible noise and prolongs battery life
  • Fan failure detection sends early warnings to facilitate predictive maintenance of UPS

Manageability

  • Intelligent battery management, including battery aging detection to evaluate battery life, and 3-stage charging functionality to reduce recharge time and extend battery life
  • Excellent local management through a user-friendly graphical and multi-lingual LCD display
  • Various types of communication interface such as dry contacts and REPO/ROO for monitoring and manageability
  • Event logs are recorded with actual time (RTC) for better management and control
Applications

UPS RT series applications

Specifications
  1. Model
    RT-5K / RT-6K / RT-8K / RT-10K

  2. Power Rating
  3. 220/230/240 V
    RT-5K: 5 kVA / 5 kW
    RT-6K: 6 kVA / 6 kW
    RT-8K: 8 kVA / 8 kW
    RT-10K: 10 kVA / 10 kW
  4. 200*/208 V
    RT-5K: 5 kVA / 4.5 kW
    RT-6K: 6 kVA / 6 kW
    RT- 8K: 8 kVA / 8 kW
    RT-10K: 10 kVA / 10 kW

  5. Input
  6. Voltage Range: 100~280 V, 100~175 V with linear de-rating 50~100%
  7. Frequency: 40~70 Hz
  8. Power Factor: > 0.99 (full load)
  9. iTHD: < 3%

  10. Input Connection
  11. Standard Runtime Model
    RT-5K: NEMA L6-30P
    RT-6K/8K/10K: Terminal
  12. Extended Runtime Model: Terminal

  13. Output
  14. Power Factor: Unity **
  15. Voltage: 200*/208/220/230/240 Vac
  16. Frequency: 50/60 Hz
  17. Voltage Harmonic Distortion: ≤ 2% (linear load)
  18. Overload Capability
    ≤ 105%: Continuous
    105~125%: 2 mins
    125~150%: 30 secs
    150%: 500 ms

  19. Receptacle
  20. Standard Runtime Model
    RT-5K: L6-20 x 2, L6-30 x 1, Load bank: L6-30 x 1
    RT-6K: L6-20 x 2, L6-30 x 1, Terminal x 1, Load bank: L6-30 x 1
    RT-8K: L6-20 x 2, L6-30 x 2, Terminal x 1, Load bank: L6-30 x 1
    RT-10K: L6-20 x 2, L6-30 x 2, Terminal x 1, Load bank: L6-30 x 1
  21. Extended Runtime Model: Terminal x 1, Load bank: Terminal x 1

  22. Efficiency
  23. AC-AC: Up to 95.5%
    ECO Mode: Up to 98.5%

  24. Battery Voltage
  25. Standard Runtime Model
    RT-5K: 192 Vdc
    RT-6K: 192 Vdc
    RT-8K: 240 Vdc
    RT-10K: 240 Vdc
  26. Extended Runtime Model: 144 Vdc ***, 192~240 Vdc

  27. Charger Current
  28. Standard Runtime Model
    RT-5K/6K: 1 A (default)
    RT-8K/10K: 1.5 A (default)
  29. Extended Runtime Model: Up to 8 A

  30. Discharge Time (Standard Runtime Model)
  31. Full load
    RT-5K: 5 min.
    RT-6K: 3 min.
    RT-8K: 5 min.
    RT-10K: 3.5 min.
  32. 75% load
    RT-5K: 7.5 min.
    RT-6K: 5.5 min.
    RT-8K: 9 min.
    RT-10K: 6 min.

  33. Recharge Time: Standard Runtime Model: 3 hrs to 90%

  34. Audible Noise
    RT-5K/6K: 48 dB
    RT-8K/10K: 50 dB

  35. Display: Graphical and multi-lingual LCD

  36. Communication
  37. Interfaces
    Mini Slot x 1, RS-232 Port x 1, RS-485 Port x 1, USB Port x 1, REPO/ROO, Dry Contact x 4

  38. Dimensions (W x D x H)
  39. Standard Runtime Model
    RT-5K/6K: 17.3 x 26.2 x 6.9 in (440 x 665 x 176 mm)
    RT-8K/10K: 17.3 x 29.5 x 8.6 in (440 x 750 x 218 mm)
  40. Extended Runtime Model
    RT-5K/6K: 17.3 x 16.9 x 3.3 in (440 x 430 x 88 mm)
    RT-8K/10K: 17.3 x 22.2 x 3.3 in (440 x 565 x 88 mm)
  41. VRLA Battery Pack
    RT-5K/6K: 17.3 x 22.2 x 3.5 in (440 x 565 x 88 mm)
    RT-8K/10K: 17.3 x 25.6 x 5.1 in (440 x 650 x 130 mm)
  42. Li-lion Battery Pack (only applicable to Extend Runtime Model):
    17.3 x 25.4 x 3.5 in (440 x 646 x 88 mm)

  43. Weight
  44. Standard Model
    RT-5K: 121.2 lbs (55 kg)
    RT-6K: 121.2 lbs (55 kg)
    RT-8K: 189.6 lbs (86 kg)
    RT-10K: 189.6 lbs (86 kg)

  45. Environment
  46. Operating Temperature: 32~131°F (0~50°C) ****
    Relative Humidity: 5~95% (non-condensing)

  47. * Under 200 V, de-rating to 90% load
    ** Under 200/208 V, 5kVA standard runtime model O/P PF = 0.9
    *** De-rating to 80% load
    **** Full load @ 32~104°F (0~40°C), de-rating to 75% @ 104~131°F (40~55°C)

    All specifications are subject to change without prior notice.

Run Time
  1. Standard Model
  2. Power Rating Internal Battery External Battery Cabinet Quantity Run time at different load (mins)
    25% 50% 75% 100%
    5 kVA Yes 0 35.6 15.6 8.9 5.6
    1 68.0 31.0 19.0 13.0
    2 106.0 51.0 32.0 22.6
    3 145.5 71.5 45.5 32.5
    4 185.0 91.5 59.0 42.5
    6 kVA Yes 0 24.3 9.6 5.6 3.1
    1 50.0 22.0 13.0 8.5
    2 79.5 37.0 22.5 15.5
    3 109.0 52.0 32.5 22.5
    4 137.0 67.0 42.5 30.0
    8 kVA Yes 0 36.3 15.6 9.3 5.1
    1 71.0 27.0 14.5 9.6
    2 119.0 49.5 27.5 17.5
    3 167.5 73.5 42.5 27.5
    4 217.0 98.0 58.0 39.0
    10 kVA Yes 0 30.2 11.9 6.2 3.7
    1 53.0 19.4 10.5 7.4
    2 91.0 36.0 19.5 12.5
    3 130.0 54.8 30.5 19.5
    4 170.0 74.0 42.5 28.0
  3.  
  4. Extended Model
  5. Power Rating External Battery Cabinet P/N External Battery Cabinet (EBC) Quantity Run time at different load (mins)
    25% 50% 75% 100%
    5 kVA BBU161B107035 1 35.2 15.2 7.8 5.1
    2 61.0 27.0 16.5 11.0
    3 96.0 45.5 28.0 19.5
    4 131.0 63.5 40.0 28.5
    BBU201B109035 1 50.0 18.5 10.3 7.3
    2 123.5 53.2 30.0 19.3
    3 199.5 91.0 54.2 36.0
    4 276.4 130.0 79.5 54.5
    6 kVA BBU161B107035 1 24.3 9.6 5.6 3.1
    2 50.0 22.0 13.0 8.5
    3 79.5 37.0 22.5 15.5
    4 109.0 52.0 32.5 22.5
    BBU201B109035 1 39.0 14.2 8.2 6.0
    2 100.5 41.4 22.5 14.5
    3 164.4 72.5 42.0 27.5
    4 228.5 105.0 63.0 42.5
    8 kVA BBU201B109035 1 36.3 15.6 9.3 5.1
    2 71.0 27.0 14.5 9.6
    3 119.0 49.5 27.5 17.5
    4 167.5 73.5 42.5 27.5
    10 kVA BBU201B109035 1 30.2 11.9 6.2 3.7
    2 53.0 19.4 10.5 7.4
    3 91.0 36.0 19.5 12.5
    4 130.0 54.8 30.5 19.5