Power Distribution Unit

For power distribution requirements of medium to large data centers, Delta’s Power Distribution Unit (PDU) is an optimal solution. The space-saving PDC is easy to move and adapt to the future demands of the data center. The PDC offers superior power protection and monitoring, and the flexibility and scalability to match your actual power distribution requirements. Not only does it improve availability, it reduces the cost of your initial investment.

Power Distribution Cabinet

Product available regions :

North America Latin America
 


Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Convenience

  • 10” Touch Panel offers intuitive interface and supports multiple languages
  • Real-time and optional billing grade metering system for actual load to the individual breaker level
  • Full front access is easy for maintenance and space saving
  • Records more than 10,000 event logs
  • Optional multi tap transformers for voltage adjustment

Reliability and Safety

  • Natural convection cooled design avoids fan failure and replacement
  • Compartmentalized electrical components provide easy and safe access
  • Redundant aux-power to enhance the reliability and availability
  • K-factor isolation transformer enhances safety and reduces harmonics
  • Built-in TVSS and lightning surge protection module
  • Built-in IR scan portholes for thermal monitoring

Availability

  • Easy to relocate, reducing investment costs
  • Highly energy efficient DOE-compliant copper transformers minimize losses and save operating cost
  • Almost all electrical components including PCB, circuit breakers and SPD devices and others are pluggable and easy to maintain (lower MTTR)
  • A wide range of breaker options to meet various
  • Top and bottom cable entry reserved installed flexibility
  • Optional floor stand (can meet seismic) and eases raised floor installations.
Specifications
  1. Capacity: 225~1000 KVA

  2. Input
  3. Rated Voltage: 480 V (Optional: 600 V)
  4. Connection: 3-Phase 3-Wire + Ground
  5. Frequency: 50/60 Hz
  6. Breaker: Optional

  7. Output
  8. Rated Voltage: 415/240 V or 208/120 V
  9. Connection: 3-Phase 4-Wire + Ground
  10. Frequency: 50/60 Hz
  11. Neutral Rating: 100% (Optional: 200%)
  12. Sub-Feed Breaker: 250/400/600 A
  13. Mounting Type: Fixed or Plug-in

  14. Transformer
  15. Rating: K-4 (Optional K-9, K-13, K-20)
  16. Efficiency: DOE 2016 Compliant

  17. Display: 10” Color Touch Screen

  18. Metered Values
  19. Input
    Phase voltage, line voltage, phase current, line current, load(%), iTHD, total kVA, total kW, total kWh, Over voltage/over current alarm, under-voltage/ under current alarm, Over line current alarm, iTHD abnormal alarm
  20. Total Output
    Phase voltage, line voltage, phase current, line current, frequency, neutral current, load(%), kVA, kW, kWh, power factor, VTHD, iTHD, Over voltage/over current alarm, under-voltage/under current alarm, Over line current alarm, iTHD abnormal alarm, VTHD abnormal alarm, power factor abnormal alarm
  21. Output Shunt Plate
    Phase current, kVA, kW, kWh, load (%), iTHD, power factor, line current, over current alarm, under current alarm, Over line current alarm, iTHD abnormal alarm, power factor abnormal alarm
  22. Output Shunt
    Current, load (%), over current alarm, under current alarm
  23. Temperature
    Environment (instant and alarm), transformers (two stage-alarm)

  24. Communication
  25. Protocol
    Modbus RTU, Modbus TCP/IP, SNMP, Ethernet
  26. Dry Contact
    Input dry contact x 14, Output dry contact x 6

  27. Compliance
  28. Safety: UL891
  29. FCC: FCC Part 15, Class A
  30. Seismic: GR63 Zone4

  31. Environment
  32. Storage Temperature: -4 to 158°F (-20 to 70°C)
  33. Operating Temperature: 32 to 104°F (0 to 40°C)
  34. Relative Humidity: 0 to 95%, Noncondensing
  35. Altitude: < 2000 m (6600 feet)

  36. Please contact Delta personnel for further information or customized requirements of your application.