DPM Gen2 Series 600-2500 kVA (480V)

Uplevel Performance, Ensure Protection

Selected by leading global cloud providers, Delta’s DPM Gen2 introduces advanced features for enhanced efficiency and reliability. This includes OPEX savings with up to 97.5% AC-AC efficiency and improved grid stability. Synchronized Multiple Bus (SMB) and parallel scalability ensures flawless reliability, making it the ideal solution for fortified hyperscale data centers.



 


 


Product available regions :
North America Latin America


Downloads (EN) Request a Quote

Product Introduction

Features & Benefits

OPEX Savings

  • AC-AC efficiency up to 97.5%, efficiency optimization at light loads saves energy costs
  • Clean mode (voltage independent mode) up to 99.2% efficient guarantees the optimum power condition while maintaining the highest level of efficiency
  • Optimizes energy cost with off-peak charging, avoiding peak-time expense
  • Elevates grid stability through responsive demand reduction and fast frequency regulation, triggers upon utility requests for eligible bill subsidies
 

Impeccable Reliability

  • Assures smooth power transitions with integrated Synchronized Multiple Bus (SMB), minimizing transformer inrush currents and maintaining balanced power from dual sources
  • Parallels up to 8 units for redundancy or expansion, supported by N+1 internal redundancy in power modular configuration
  • Maximizes UPS performance and lifespan with self-diagnosis and key component analysis
 

Ultimate Availability

  • Lithium-ion battery ready. Adjustable battery charging voltage adapts to multiple types of batteries
  • Seamless power shifts to generator with an advance power walk-in function, pausing during frequency issues for smooth transitions without unnecessary generator sizing expansion
  • Grid interactive application. Provides corrective operation for unstable renewal energy sources with an innovative topology design that handles grid and battery power at the same time
  • Easy mounting/cabling that supports both top and bottom cable entry and full front access
 
Applications

UPS EH Series applications

Specifications
  1. Model
  2. DPM G2-600K(1), DPM G2-900K, DPM G2-1200K, DPM G2-1500K, DPM G2-1800K, DPM G2-2100K, DPM G2-2400K(1), DPM G2-2500K

  3. Power Rating
  4. ⦁ DPM G2-600K: 600 kVA / 600 kW
    ⦁ DPM G2-900K: 900 kVA / 900 kW
    ⦁ DPM G2-1200K: 1200 kVA / 1200 kW
    ⦁ DPM G2-1500K: 1500 kVA / 1500 kW
    ⦁ DPM G2-1800K: 1800 kVA / 1800 kW
    ⦁ DPM G2-2100K: 2100 kVA / 2100 kW
    ⦁ DPM G2-2400K: 2400 kVA / 2400 kW
    ⦁ DPM G2-2500K: 2500 kVA / 2500 kW
  5. Parallel Configuration: Up to 8 units

  6. Input
  7. Nominal Voltage: 480 Vac, 3P3W+PE
  8. Voltage Range: 408-552 Vac (100% load)
  9. Frequency Range: 40-70 Hz
  10. Total Harmonic Distortion (THDi): < 3% (100% resistive load)
  11. Power Factor: > 0.99 (100% load)
  12. Short Circuit Withstand Rating
    ⦁ DPM G2-600~1200K: 65 kA
    ⦁ DPM G2-1500~2500K: 100 kA

  13. Output
  14. Nominal Voltage: 480 Vac, 3P3W+PE
  15. Voltage Regulation: ±1% (static)
  16. Frequency: 50/60 ± 0.05 Hz
  17. Total Harmonic Distortion (THDv): < 1% (linear load)
  18. Overload Capability: < 110%: continues, 110-125%: 10 mins, 126-150%: 1 min, > 150%: 1 sec
  19. Current Crest Ratio: 3:1

  20. Efficiency
  21. Online Mode: Up to 97.5%
  22. Clean Mode (VI): Up to 99.2%

  23. Battery
  24. Battery Type: VRLA, Vented lead-acid, Lithium-ion, Ni-Zinc
  25. Nominal Voltage: 480 Vdc
  26. Quantity: 34-35(2), 36-46 pcs (Configurable, 12V VRLA battery)
  27. Charge Current
    ⦁ DPM G2-900K: 375 A
    ⦁ DPM G2-1200K: 500 A
    ⦁ DPM G2-1500K: 625 A
    ⦁ DPM G2-1800K: 750 A
    ⦁ DPM G2-2100K: 1000 A
    ⦁ DPM G2-2500K: 1125 A
  28. Protection Design: Battery shunt trip x1, Battery temperature detection x4, Battery breaker status dry contact x1

  29. Communication Interfaces
  30. Display: 10-inch color touchscreen
  31. Port:
    Smart slot x2, Modbus (RS-485) port x1, REPO port x1, Input dry contact x6, Output dry contact x6, Synchronized Multiple Bus (SMB) x2, Breaker status detection x4, EMS/Console port x1, Ethernet x1
  32. Protocols: SNMP, Modbus RTU, Modbus TCP/IP, HTTP(S), SNTP, SMTP, BOOTP, DHCP

  33. Physical
  34. Dimensions (W x D x H) 
    ⦁ DPM G2-900K: 2710 x 990 x 2000 mm
    ⦁ DPM G2-1200K: 3070 x 990 x 2000 mm
    ⦁ DPM G2-1500K: 3400 x 990 x 2000 mm
    ⦁ DPM G2-1800K: 4530 x 990 x 2000 mm
    ⦁ DPM G2-2100K: 4870 x 990 x 2000 mm
    ⦁ DPM G2-2500K: 5903 x 990 x 2000 mm
  35. Net Weight
    ⦁ DPM G2-900K: 2026 kg
    ⦁ DPM G2-1200K: 2408 kg
    ⦁ DPM G2-1500K: 2779 kg
    ⦁ DPM G2-1800K: 4174 kg
    ⦁ DPM G2-2100K: 4551 kg
    ⦁ DPM G2-2500K: 5820 kg

  36. Environment
  37. Operating Temperature: 32 to 104°F (0 to 40°C)
  38. Humidity: 0-95% (non-condensing)
  39. Altitude: 0-6562 ft (derating 1%/328 ft from 3280-6562 ft)

  40. Conformance
  41. Safety: UL
  42. EMC: FCC Class A
  43. Performance: IEC 62040-3
  44. Sustainability: RoHS, REACH, Energy Star 2.0

  45. Features
  46. Standard
    ▪️ Advance Power Walk-in for Generator
    ▪️ Backfeed Protection with Contactor
    ▪️ Burn-in Test without Load Bank
    ▪️ Cold Start Function
    ▪️ Synchronized Multiple Bus (SMB)
    ▪️ Battery Shunt Trip
    ▪️ Auxiliary Power 48 Vdc for Shunt Trip
    ▪️ Failure Prediction
  47. Optional
    ▪️ Grid Interactive
    ▪️ Software Integration with Delta Lithium-ion Battery BMS
    ▪️ DC Battery Ground Fault Detector
    ▪️ Integrated Battery Switch Cabinet
    ▪️ IR Scan Window

  48. (1) Upcoming product
    (2) 34-35 pcs require service setting and load derating
  49. All specifications are subject to change without prior notice.