HPH Series 20/30/40/60 kVA (208/120 V)

Best-in-class power protection with maximum power and cost efficiency

The Ultron HPH is a true online double-conversion UPS offering the best-in-class combination of maximum available power, unbeatable energy efficiency and superior power performance for small data centers and other mission critical applications . With fully rated power (kVA=kW), the Ultron HPH provides maximum available power without de-rating the UPS. Thanks to the three level IGBT topology for both PFC (power factor correction) and inverter, the Ultron HPH features up to 94% AC-AC efficiency. Delta’s advanced digital PFC control also contributes low iTHD < 3% and high input power factor > 0.99 resulting in significant TCO (Total Cost of Ownership) savings. Facilitating increased availability and power performance, the Ultron HPH is an ideal solution for protecting your mission critical operations.

 HPH Series UPS, Three Phase, 20/30/40/60 kVA/kW, 208/120V

Product available regions :

North America Latin America


Downloads Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

Best-in-Class Power Performance and Efficiency

  • Fully rated power (kVA=kW) for maximum power availability
  • Leading AC-AC efficiency up to 94% saves energy costs
  • Low harmonic pollution (iTHD < 3%) and high input power factor (> 0.99) reduce upstream investment costs

Assured Reliability

  • Parallel expansion and N+X redundancy up to 4 units
  • Redundant auxiliary power and fan design enhance system reliability
  • Optional IPX1 level protection

Greater Flexibility

  • A wide choice of configurations, such as N+X redundancy and hot stand-by
  • Adjustable charging current and charging voltage meet different battery configuration requirements
  • Flexible battery configuration optimizes battery investment

Superior Serviceability and Management

  • Front-door battery replacement with hot-swappable battery tray design supports easy and quick replacement without turning the unit off
  • Swappable interior architecture and front access servicing enables quick and easy maintenance
  • Multi-connectivity interface supports remote UPS monitoring and management
Applications

UPS HPH Series applications

Specifications
  1. Model
  2. Integrated Bbattery Model - with battery:
    HPH-20K-LV-B / HPH-30K-LV-B / HPH-40K-LV-B / HPH-60K-LV-B
  3. Integrated Battery Model - without battery:
    HPH-20K-LV-BN / HPH-30K-LV-BN / HPH-40K-LV-BN / HPH-60K-LV-BN

  4. Power Rating
  5. HPH-20K-LV: 20 kVA / 20 kW
    HPH-30K-LV: 30 kVA / 30 kW
    HPH-40K-LV: 40 kVA / 40 kW
    HPH-60K-LV: 60 kVA / 60 kW

  6. Input
  7. Nominal Voltage: 208/120 Vac, 220/127 Vac (3 phase, 4-wire + G)
  8. Voltage Range: 125~253 Vac (L-L) / 72~146 Vac (L-N) *
  9. Frequency Range: 40~70 Hz
  10. Power Factor: > 0.99 (full load)
  11. Current Harmonic Distortion: < 3%

  12. Output
  13. Voltage: 208/120 Vac, 220/127 Vac (3 phase, 4-wire + G)
  14. Voltage Regulation: ± 1%
  15. Voltage Harmonic Distortion: < 3% (linear load)
  16. Overload Capability
    < 105%: continuous
    105~125%: 10 minute
    125~150%: 1 minute
    > 150%: 0.5 second
  17. Output Power Factor: 1
  18. Frequency: 50/60 Hz ± 0.05 Hz

  19. Battery
  20. Battery Quantity: Adjustable ± 11~13 pcs (default 12 pcs)
  21. Type: Support SMF and VRLA
  22. Charge Current (Max.): 10 A
  23. Charge Voltage
    Float charge 163 ± 3 Vdc
    Boost charge 168 ± 3 Vdc (default 12 pcs)
  24. Backup Time **
    HPH-20K-LV: 9.5 min (9Ah x 48pcs)
    HPH-30K-LV: 9.5 min (9Ah x 72pcs)
    HPH-40K-LV: 6.5 min (9Ah x 72pcs)
    HPH-60K-LV: 5.2 min (9Ah x 96pcs)

  25. Communication Interfaces
  26. SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6

  27. Display
    LED indicators and Multi-language LCD display

  28. Conformance
    Safety: UL, cUL, Energy Star

  29. Other Features
    Parallel Redundancy: Up to 4 units
  30. Emergency Power Off: Local and remote

  31. Efficiency
  32. AC-AC Mode: Up to 94%
  33. ECO Mode: Up to 98%

  34. Environment
  35. Operating Temperature: 0~40°C
  36. Ambient Storage Temperature: -20~40°C
  37. Relative Humidity: 0~95% (non-condensing)
  38. Audible Noise
    HPH-20K-LV: < 65 dBA
    HPH-30K-LV: < 65 dBA
    HPH-40K-LV: < 70 dBA
    HPH-60K-LV: < 70 dBA

  39. Physical
  40. Dimensions (W x D x H)
    HPH-20K-LV: 520 x 800 x 1380 mm
    HPH-30K-LV: 520 x 800 x 1380 mm
    HPH-40K-LV: 520 x 800 x 1760 mm
    HPH-60K-LV: 520 x 800 x 1760 mm
  41. Weight (with battery)
    HPH-20K-LV-B: 340 kg
    HPH-30K-LV-B: 420 kg
    HPH-40K-LV-B: 450 kg
    HPH-60K-LV-B: 530 kg
  42. Weight (without battery)
    HPH-20K-LV-BN: 196 kg
    HPH-30K-LV-BN: 204 kg
    HPH-40K-LV-BN: 224 kg
    HPH-60K-LV-BN: 242 kg

  43. HPH-20K-LV-B: UPS integrated battery model has batteries inside
    HPH-20K-LV-BN: UPS integrated battery model has no batteries inside

    * When input voltage range is 72~108Vac(L-N) and 125~187Vac(L-L), the sustainable loading is from 63% to 100% of UPS capacity.
    ** At 70% load with internal battery strings.

    All specifications are subject to change without prior notice.