NT Series 15-100 kVA (480 V)

Enterprise power customized for greatest reliability

The Ultron NT series is a three phase UPS featuring customized I/P-O/P ratings for various applications. With N+X parallel redundancy or expansion, it guarantees high availability and reliability for your critical loads.

The Ultron NT series offers continued seamless protection for your business even under 100% unbalanced loading conditions. Its economy mode improves efficiency and saves operating cost.


Product available regions :

North America Latin America
(20–500 kVA)


Downloads Request a Quote Subscribe Newsletter

Product Introduction

Features & Benefits

 

  • Parallel redundancy without requiring extra hardware to increase reliability.
  • Built-in isolation transformer protects user equipment.
  • Redundant auxiliary power and control circuit ensures higher reliability.
  • Inbuilt maintenance and static bypass switch.
  • Multi-language LCD display and LED status indicators.
  • RS232, RS485 and six programmable dry contact outputs.
  • Compatible with generator installation and unbalanced loads.
  • Parallel expansion as your business grows and consequently saves initial investment.
  • Wide input voltage range extends battery lifetime.
  • 12-pulse SCR rectifier and full-bridge Inverter design.
  • Common battery installation saves initial investment.
Applications

UPS NT Series applications

Specifications
  1. Model
  2. NT-15K / NT-30K / NT-60K / NT-100K

  3. Power Rating
  4. NT-15K: 15 kVA / 13.5 kW
    NT-30K: 30 kVA / 27 kW
    NT-60K: 60 kVA / 54 kW
    NT-100K: 100 kVA / 90 kW

  5. Input
  6. Nominal Voltage: 480 V (3 phase, 4-wire+G)
  7. Voltage Range: ± 20%
  8. Nominal Frequency: 50/60 Hz
  9. Frequency Range: ± 5%
  10. Nominal Current
    NT-15K: 25 A
    NT-30K: 50 A
    NT-60K: 97 A
    NT-100K: 160 A

  11. Output
  12. Nominal Voltage: 208/120 V (3Æ4W+G)
  13. T.H.D.(with linear load): ≤ 3%
  14. Voltage Regulation:
    static: ± 1%; dynamic: ± 5%
  15. Inverter Overload Capability
    110%: 60 min
    125%: 10 min
    150%: 1 min
  16. Nominal Frequency: 50/60 Hz
  17. Frequency Regulation
    with internal oscillator: ± 0.01%
    with mains synchronize: 1%
  18. Static Switch Overload Current
    30 minutes: 120%
    30 milliseconds: 1000%
  19. Transfer Time: 0

  20. Alarm
  21. Load on Battery: Discontinuous alarm
  22. UPS Abnormal: Continuous alarm

  23. Interface
  24. LED Status Indication
    UPS status indication: AC mains normal, reserve source normal, rectifier, inverter, static switch, and battery status indication
  25. LCD Display
    UPS abnormal status display and self-diagnosis wisely
    Input, bypass, inverter, output & battery voltage, current and frequency, load level display

  26. Remote
  27. Monitor
    Multi-unit monitor, graphic display, and history data statistics
  28. Control
    Inverter/horns remote control, password setting, fault information reading, and remote alarm

  29. Function
  30. Communication Interface
    Standard: RS232, RS485, Status Dry Contact
    Option: SNMP, Ethernet Port
  31. Parallel Redundant: Yes (up to 8 UPS)
  32. Emergency Power Off: Yes (Local and Remote)
  33. Multi-speed Fan Speed Control: Yes
  34. SRAM Fault Sequence Memory: Yes
  35. Programmable Parameter Setting: Yes
  36. Battery Start Function: Yes
  37. Input Harmonic Improvement: 12-pulse rectifier

  38. Environment
    Ambient Temperature: 0~40ºC
    Relative Humidity: 90% (non-condensing)
    Operating Elevation: 0~2000 meters (0~6060 ft)

  39. Audible Noise (at 1.5 meters)
    NT-15K/30K: ≤ 60 dB
    NT-60K/100K: ≤ 65 dB

  40. Physical
  41. Dimensions (W x D x H)
    NT-15K/30K: 600 x 800 x 1400 mm
    NT-60K: 800 x 830 x 1700 mm
    NT-100K: 1200 x 830 x 1700 mm
  42. Weight
    NT-15K: 402 kg
    NT-30K: 502 kg
    NT-60K: 762 kg
    NT-100K: 1125 kg

  43. All specifications are subject to change without prior notice.